Request a quoteQuote
Spirax Sarco DCV3 Disc Check Valve
Spirax Sarco

Spirax Sarco DCV3 Disc Check Valve

The DCV3 and DCV3LT disc check valves are of the wafer pattern designed to be sandwiched between flanges.

Read more

The DCV3 and DCV3LT disc check valves are of the wafer pattern designed to be sandwiched between flanges. They are suitable for use on a wide range of fluids for applications in process lines, hot water systems, steam and condensate systems etc. Face-to-face dimensions conform to EN 558 part 1, series 49.

As standard they are supplied with a metal-to-metal seat for use on steam applications; for oil, air, gas and water applications alternative seat materials are available. Disc check valves are opened by the pressure of the fluid and closed by the spring as soon as the flow ceases and before the reverse flow occurs.

Key data

  • Sizes: DN15, DN20, DN25, DN32, DN40, DN50, DN65, DN80 and DN100
  • Installation: between BS 10 Tables 'E' and 'H', EN 1092 PN6, PN10, PN16, PN25 and PN40, JIS 5, JIS 10, JIS 16 and JIS 20 flanges (DN40, DN50, DN80 and DN100 will not fit between JIS 5 flanges; DN65 and DN80 will not fit between BS 10 'E' flanges)
  • Body design conditions: PN40
  • PMA (maximum allowable pressure): 40 bar g @ 50 °C
  • TMA (maximum allowable temperature): 400 °C @ 31.2 bar g
  • Minimum allowable temperature: DCV3 -10 °C; DCV3LT -60 °C
  • PMO (maximum operating pressure, metal-to-metal seat): 40 bar g @ 50 °C
  • TMO (maximum operating temperature): 300 °C @ 33.3 bar g with standard or heavy duty spring; 400 °C @ 31.2 bar g with high temperature spring (DCV3 only) or without spring
  • Seat temperature limits: Viton from -25 °C to 205 °C; EPDM from -40 °C to 120 °C
  • Body: austenitic stainless steel WS 1.4581
  • Standard shut-off: EN 12266 rate E; rate D on request; soft seated versions rate A, providing a differential pressure exists
  • Standards: European Pressure Equipment Directive 2014/68/EU
  • Certification: Typical Test Report; certification to EN 10204 3.1 available

Key features

  • Optional heavy duty springs (700 mbar opening pressure, up to DN65) for boiler feed applications
  • Optional Viton soft seats for oil, air and gas applications and EPDM soft seats for water applications
  • DCV3 Food+ DN15 to DN100 (metal seat and EPDM seat) available with a food contact regulation Declaration of Compliance: (EC)1935:2004, (EC)2023:2006, (EU)10/2011 and FDA Code of Federal Regulations title 21
  • The DCV3LT is supplied with 'LT' stamped on the unit

Category

20 codes

Representative image

Code not listed? Send us the code

Fast worldwide delivery · reply within 12 working hours

Request a quote for Spirax Sarco